Commercial maintenance guide

NFPA 96 hood inspection & cleaning in Orlando

Florida commercial exhaust maintenance distinguishes scheduled inspections for grease buildup from cleaning when deposits are found. The hood, accessible ductwork and fan must be considered together; confirm the applicable requirements with the local fire authority.

What does NFPA 96 cover?

NFPA 96 addresses ventilation control and fire protection for commercial cooking. The exhaust route includes the hood, grease filters, ductwork and exhaust fan. Cleaning only the visible canopy does not establish the condition of concealed components. Ordinary household range hoods are not automatically subject to this commercial schedule.

Are these inspection or cleaning intervals?

The schedule is for inspection for grease buildup: monthly for solid-fuel operations; quarterly for high-volume operations such as 24-hour cooking, charbroiling or wok cooking; semiannually for moderate volume; annually for low-volume operations such as churches, camps or seasonal businesses. Cleaning is required when grease deposits are found. Do not wait for the next scheduled interval if inspection already identifies contamination.

Which Florida code applies?

As reviewed in November 2026, the Florida State Fire Marshal identifies the 8th Edition Florida Fire Prevention Code as effective December 31, 2023 and lists the next edition as effective December 31, 2026. Local officials enforce the applicable code and local amendments. Confirm the current requirements for the actual kitchen with its local authority; this guide does not replace official interpretation.

What should be recorded after service?

Keep the dated scope, system identification, photographs where available and a clear list of inaccessible or uncleaned areas. Do not treat a service sticker as an inspection guarantee. Retain earlier reports so repeated access problems and grease leaks are visible to the kitchen manager and property owner.

What if duct sections cannot be reached?

An access limitation must be recorded, not hidden behind a general completion statement. Suitable access-panel planning may be necessary before the section can be cleaned. Duct construction, enclosure requirements and approvals require assessment before alteration; a ceiling hatch alone does not provide access to the duct interior.

What warning signs deserve assessment?

Grease dripping at filters, smoke escaping into the room, roof grease leaks and new fan noise deserve attention. Some symptoms involve cleaning; others require mechanical, electrical or ventilation assessment. A cleaning appointment should not be sold as a guaranteed fix for every performance or safety concern.

Where can you verify the requirements?

Reviewed November 2026. This is general guidance, not legal advice or a guarantee of inspection approval. The local authority determines applicable requirements.